Method for improving current carrying capacity of 110 kV cross-linked polyethylene cable
CSTR:
Author:
Affiliation:

(1.School of Electrical Engineering and Automation, Xiamen University of Technology, Xiamen 361024, China;2.Xiamen Key Laboratory of Frontier Electric Power Equipment and Intelligent Control, Xiamen 361024, China;3.State Grid Fujian Electric Power Company Xiamen Power Supply Company, Xiamen 361006, China;4.Sun Submarine Cable (Dongshan) Co., Ltd., Zhangzhou 363400, China )

Clc Number:

TM757

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    To address the issues of low land resource utilization efficiency in cable trench installation and poor heat dissipation in conduit trench installation, a magnetic-thermal-current multiphysics coupled finite element simulation model of a 110 kV cross-linked polyethylene cable was constructed. The current carrying capacity of both the cable trench and the conduit trench installation methods was simulated and calculated. The effects of three methods, laying concrete outside the conduit in the conduit trench installation method, using high thermal conductivity conduits, and adding backfill materials inside the conduit, on increasing the current carrying capacity of the cable were investigated. Based on the orthogonal experiment, the backfill material was improved to obtain the optimal ratio of the backfill material. The research results show that by pouring concrete outside the high thermal conductivity conduits and adding improved backfill materials with the optimal proportion inside the conduit, the current carrying capacity of the cable can be significantly enhanced. Compared with the cable trench installation method, this approach increases single-circuit capacity by 31.64% and dual-circuit capacity by 18.49%.

    Reference
    Related
    Cited by
Get Citation

朱婷,林宇辰,严有祥,等.110. kV交联聚乙烯电缆载流量提升方法[J].河海大学学报(自然科学版),2025,53(6):158-165.(ZHU Ting, LIN Yuchen, YAN Youxiang, et al. Method for improving current carrying capacity of 110 kV cross-linked polyethylene cable[J]. Journal of Hohai University (Natural Sciences),2025,53(6):158-165.(in Chinese))

Copy
Related Videos

Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:December 14,2024
  • Revised:
  • Adopted:
  • Online: December 09,2025
  • Published:
Article QR Code